Woodcore Raised Floor

WC Series WoodCore Raised Floor System


Unifloor’s WC Series Panel system sets the standard for acoustic relief and easy work-ability. Unifloor’s wood core panel has been designed with superior resin bonded particle board, creating a high quality product with enhanced strength for this height and weight class. The high density particle board core can be easily cut onsite to fit oblique perimeters and around structural details without specialist equipment.
WC  panels are available with typical data center finishes such as high pressure laminates and conductive / dissipative vinyl. The system is compatible with a full array of understructure and installation applications..

 

 

UnifloorWCtype

 

Available in 4 performance standards with a vast range of understructure products to accommodate your anticipated loading requirements.

  • WCG 800 Medium Duty with Galvanized Steel Sheet
  • WCG 1000 Heavy Duty with Galvanized Steel Sheet
  • WCA 800 Medium Duty with Aluminum Sheet
  • WCA 1000 Heavy Duty with Aluminum Sheet

 

Unifloorwcpanel
The Unifloor raised flooring range made of high-density particle board panels is very widely used. These panels comply to the European Standard EN12825 and are tested in accordance to the EN 13501. Moreover, we also manufacture woodcore panels complying with the British PSA/MOB Standard, with much higher requirements in terms of load class. The standard dimension is 600x600 mm, but upon request, other dimensions are available. .
 
Panel Grade Point Load (Kgs) Ultimate Load (Kgs/Sqm) Uniform Load (Kgs/Sqm) Rolling Load 10/10,000 Pass (Kgs) Safety Factor Tender Spec Sheet
WCG800 360 1080 1650 310 / 210 2 xlsxicon
WCG1000 450 1650 2150 360 / 310 2 xlsxicon
WCA800 360 1080 1650 450 / 360 2 xlsxicon
WCA1000 450 1650 2150 550 / 450 2 xlsxicon
*Manufacturer reserves the right to Modify specification without prior intimation.

Concentrated Load

pointload
The maximum deflection and permanent set of an access floor panel under load. When testing for a panel's concentrated load, a 25 x 25mm2 load is applied onto the surface of the panel at its weakest point.The panel deflection and permanent set is measured by recording the indentor movement. The panel must bear applied load and not crack.

Ultimate Load

ultimate
The Maximum load applied onto the panel uptil failure. When testing for a panel's ultimate load, a concentrated 25 x 25mm2 load is applied onto the surface of the access floor panel and this load is increased until the panel fails structurally.

Uniform Load

uniformload
Uniform load is static force equally applied over the entire area of the panel and is typically imposed by stationary furniture and equipment without legs. The uniform load rating is specified in Kgs per square metre. he panel deflection and permanent set is measured by recording the indentor movement. The panel must bear applied load and not crack.

Rolling Load

rolling
The durability and/or deformation of an access floor system when exposed to commercially anticipated caster traffic using a specific load. Rolling loads are defined by the number of passes, size and hardness of the wheel, and the combined weight of the cart and its contents on each wheel.

Axial Load

axial
Axial load is a vertical load applied to the centre of the pedestal due to concentrated, rolling, uniform and other loads applied to the surface of the access floor panel that is transferred to the pedestal.